Operating Instructions

Communication via AS-i - only for G110M
7.1 Setting the address
Fieldbuses
218 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Addressing via the addressing device (e.g. 3RK1904-2AB02)
Addressing via the addressing device is made offline.
Further information is contained in the AS-Interface system manual, Section "Setting the AS-i
address"
Overview of the manuals (Page 232)
Addressing via parameters
The address assignment is made with the p2012[0] and p2012[1] parameters.
If you assign the address via Startdrive, you must back up the settings so that they are not
lost if the power fails.
Address range for Single Slave inverter, profile 7.F.E
p2012[1]: 0 … 31, range for the A address, 0A31A
Address range for Dual Slave inverter, profile 7.A.5 or 7.A.E
p2012[0]: 0 … 31, 3363 for slave 1:
p2012[1]: 0 … 31, 3363 for slave 2:
with
0 … 31 range for the A address, 0A31A
3363 range for B address, 1B31B