Note: For U/f control and sensorless vector control (see p1300), ramp-down times of 0 s are not recommended. The set-
ting should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1127 is re-calculated.
Description: Sets the minimum ramp-down time.
The ramp-down time (p1121) is limited internally to this minimum value.
Dependency: Refer to: p1082
Note: For U/f control and sensorless vector control (see p1300), ramp-down times of 0 s are not recommended. The set-
ting should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1127 is re-calculated.
If a braking resistor is connected to the DC link (p0219 > 0), then the minimum ramp-down time is automatically
adapted using p1127.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
p1127[0...n] Ramp-function generator minimum ramp-down time / RFG t_RD min
PM240
PM330
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 999999.000 [s] 0.000 [s]
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
PM230
PM330
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
PM230 Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]