Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
40 List Manual (LH9), 04/2014, A5E33838102B AA
Bit 09: r0899 Bit 7
Bit 10: r2197 Bit 6
Bit 11: r0056 Bit 13 (negated)
Bit 13: r2135 Bit 14 (negated)
Bit 14: r2197 Bit 3
Bit 15: r2135 Bit 15 (negated)
Description: Display and BICO output for status word 2.
Notice: p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
Note: The following status bits are displayed in r0053:
Bit 00: r1239 Bit 8
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
Bit 03: r2197 Bit 8
Bit 04: r2197 Bit 2
Bit 05: r2197 Bit 1
Bit 06: r2197 Bit 4
Bit 07: r2197 Bit 9
Bit 08: r2197 Bit 10
Bit 09: r1199 Bit 2 (negated)
Bit 10: r2349 Bit 10
Bit 11: r2349 Bit 11
Description: Displays control word 1.
r0053.0...11 CO/BO: Status word 2 / ZSW 2
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DC braking active Yes No -
01 |n_act| > p1226 (n_standstill) Yes No -
02 |n_act| > p1080 (n_min) Yes No -
03 I_act >= p2170 Yes No -
04 |n_act| > p2155 Yes No -
05 |n_act| <= p2155 Yes No -
06 |n_act| >= r1119 (n_set) Yes No -
07 Vdc <= p2172 Yes No -
08 Vdc > p2172 Yes No -
09 Ramp-up/ramp-down completed Yes No -
10 Technology controller output at the lower
limit
Yes No -
11 Technology controller output at the upper
limit
Yes No -
r0054.0...15 CO/BO: Control word 1 / STW 1
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Operation enable Yes No -
04 Ramp-function generator enable Yes No -