2 Parameters
2.2 List of parameters
Description: Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note: The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0).
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
Description: Sets the number of reactors connected in series at the power unit output.
Dependency: Refer to: p0230
Notice: The reactor inductances should be the same.
If the number of motor reactors connected in series does not correspond to this parameter value, then this can result
in an unfavorable control behavior.
Description: Displays the internal resistance of the power unit (IGBT and line resistance).
Description: Sets the configuration for the output voltage measurement of the power unit.
Note: The motor data identification must be executed when using the voltage measurement.
p0234 Power unit sine-wave filter capacitance / PU sine filter C
PM230
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 2), U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [µF] 1000.000 [µF] 0.000 [µF]
p0235 Motor reactor in series number / L_mot in SeriesQty
PM240 Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: C(1, 2) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 3 1
r0238 Internal power unit resistance / PU R internal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0247 Voltage measurement configuring / U_mes config
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(2), U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0010 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activate voltage measurement Yes No -
01 Siemens internal Yes No -
02 Siemens internal Yes No -
05 Use voltage measured values for flying
restart
Yes No -
07 Voltage calibration when switching on Yes No -
08 Voltage monitoring when switching on Yes No -
09 Voltage monitoring cyclic Yes No -