2 Parameters
2.2 List of parameters
Description: Display and connector output for the system deviation of the free technology controller 0.
Description: Sets the time constant for the differentiation (D component) of the free technology controller 0.
Note: Value = 0: Differentiation is deactivated.
Description: Sets the proportional gain (P component) of the free technology controller 0.
Note: Value = 0: The proportional gain is deactivated.
Description: Sets the integral time (I component, integrating time constant) of the free technology controller 0.
Note: Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
Description: Sets the maximum limit of the free technology controller 0.
Dependency: Refer to: p11092
Note: The maximum limit must always be greater than the minimum limit (p11091 > p11092).
r11073 CO: Free tec_ctrl 0 system deviation / Ftec0 sys dev
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_2 Unit selection: p11026 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
p11074 Free tec_ctrl 0 differentiation time constant / Ftec0 D comp T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p11080 Free tec_ctrl 0 proportional gain / Ftec0 Kp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 1000.000 1.000
p11085 Free tec_ctrl 0 integral time / Ftec0 Tn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.000 [s] 10000.000 [s] 30.000 [s]
p11091 CO: Free tec_ctrl 0 limit maximum / Ftec0 lim max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]