Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
361
2 Parameters
2.2 List of parameters
Description: Sets the two wire control/three wire control.
Value: 0: No wire control
1: Two wire control clockwise/counterclockwise 1
2: Two wire control clockwise/counterclockwise 2
3: Three wire control enable clockwise/counterclockwise
4: Three wire control enable ON/reversing
Dependency: Refer to: p0015, p3330, p3331, p3332, r3333
Note: This value depends on the wire control set in p0015.
Description: Sets the signal source for the start of motion dependent on the sign of the setpoint.
Dependency: Refer to: p3342, p3343, r3344
Refer to: A07352
Description: Sets the signal source for the limit switch plus.
BI: p3342 = 1-signal:
Limit switch is inactive.
BI: p3342 = 0 signal:
Limit switch is active.
Dependency: Refer to: p3340, p3343, r3344
Note: For p1113 = 0, the drive traverses with a positive speed setpoint towards the positive limit switch – or for p1113 = 1
with a negative speed setpoint.
Description: Sets the signal source for the limit switch minus.
BI: p3343 = 1-signal:
Limit switch is inactive.
BI: p3343 = 0 signal:
Limit switch is active.
Dependency: Refer to: p3340, p3342, r3344
p3334 2/3 wire control selection / 2/3 wire select
Access level: 4 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
0 4 0
p3340[0...n] BI: Limit switch start / Lim switch start
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
p3342[0...n] BI: Limit switch plus / Lim switch plus
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 1
p3343[0...n] BI: Limit switch minus / Lim switch minus
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 1