Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
103
2 Parameters
2.2 List of parameters
Note: The reference value to identify the stator resistance is determined at the first identification. This must be realized
when the motor is in a cold state, as the value refers to the ambient temperature p0625. The feeder cable resistance
should be entered into p0352 before the measurement.
The result must be saved after the first measurement so that the reference is available after the CU has powered up.
When changing p0350 or p0352, the reference value p0629 should be re-determined.
Description: Displays the ambient temperature of the motor temperature model (models 2 and 3).
Description: Displays the stator iron temperature of the motor temperature model (models 2 and 3).
Note: For motor temperature model 1 (p0612.0 = 1), this parameter is not valid:
Description: Displays the stator winding temperature of the motor temperature model.
Dependency: Refer to: F07011, A07012, A07910
Description: Displays the rotor temperature of the motor temperature model (models 2 and 3).
Note: For motor temperature model 1 (p0612.0 = 1), this parameter is not valid:
Description: Sets the current limit.
Dependency: Refer to: r0209, p0323
Note: The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0305. The current limit p0640 is limited to r0209.
The resulting current limit is displayed in r0067 and if required, r0067 is reduced by the thermal model of the power
unit.
r0630[0...n] Mot_temp_mod ambient temperature / Mod T_ambient
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
- [°C] - [°C] - [°C]
r0631[0...n] Mot_temp_mod stator iron temperature / Mod T_stator
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
- [°C] - [°C] - [°C]
r0632[0...n] Mot_temp_mod stator winding temperature / Mod T_winding
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8017, 8018
Min Max Factory setting
- [°C] - [°C] - [°C]
r0633[0...n] Mot_temp_mod rotor temperature / Mod rotor temp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
- [°C] - [°C] - [°C]
p0640[0...n] Current limit / Current limit
Access level: 2 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(1, 3), U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6640, 6828
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]