Operating Instructions
6.16.2 Invert setpoint
Function description
S
[
\
[
\
W
\ \[[
The function inverts the sign of the setpoint using a binary signal.
Example
To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal
of your choice.
Table 6-35 Application examples showing how a setpoint is inverted
Parameter Description
p1113 = 722.1 Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Inverter inverts the setpoint.
p1113 = 2090.11 Inverts the setpoint via the fieldbus (control word 1, bit 11).
Parameter
Parameter Description Setting
p1113[0…n] BI: Setpoint inversion Signal source for inverting the setpoint
1 signal: Invert setpoint
The factory setting depends on the fieldbus interface.
Advanced commissioning
6.16 Setpoint calculation
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 271