Use
Demand-controlled speed control of supply and discharge fans in air conditioning
systems
Demand-controlled speed control of circulating pumps in HVAC systems
Pressure boost and control of the fill level of pumps
Functions
Functions specific to pumps and fans are already integrated
Automatic restart
Application restarts after a power failure or a fault
Flying restart
Variable speed drive is switched in while the motor is running
ECO mode
Automatic adaptation of the motor current to the actual load conditions, e.g. for
applications with a low dynamic response and a constant speed setpoint
Motor staging
For applications that require simultaneous operation of between 1 and 4 motors
depending on load, e.g. closed-loop control of highly fluctuating flow volumes
Hibernation: Drive is started/stopped in accordance with the actual setpoints
4 integrated PID controllers
For controlling the speed of the drive as a function of pressure, temperature, flowrate,
level, air quality and other process variables
Essential Service Mode
Special operating mode of the variable speed drive that enhances the availability of the
drive system in the event of a fire
Multi-zone controller
Control of a zone with up to 3 sensors for pressure or temperature, or
Control of two independent zones, each with one sensor
Bypass mode
When the setpoint is reached or a fault occurs, there is a changeover to mains operation
Programmable time switches (x 3 units)
Real-time clock
For time-dependent process controls, e.g. temperature reduction for heating control at
night
Freely programmable logical function blocks
For simulating simple PLC functions
Motor monitoring with and without temperature sensor (via PTC, KTY and ThermoClick
sensor)
Overcurrent protection
Torque monitoring
Overvoltage protection (Vdc_max controller)
Braking function using a DC brake
Connections and interfaces
Fieldbus interface of the CU230P-2 Control Unit optionally with
RS485/USS, Modbus/RTU, BACnetMS/TP, P1 (standard delivery)
PROFIBUS DP
– CANopen
PROFINET IO
2 x LG-Ni1000-/Pt1000 interface for direct connection of temperature sensors
230 V relay for direct connection of auxiliary equipment