Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
392 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the minimum limit of the free technology controller 1.
Dependency: Refer to: p11191
Note: The maximum limit must always be greater than the minimum limit (p11191 > p11192).
Description: Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11191, p11192) of the free technology
controller 1.
Dependency: Refer to: p11191, p11192
Note: The ramp-up/ramp-down times are referred to 100%.
Description: Display and connector output for the output signal of the free technology controller 1.
Description: Sets the signal source for the maximum limit of the free technology controller 1.
Dependency: Refer to: p11191
Description: Sets the signal source for the minimum limit of the free technology controller 1.
Dependency: Refer to: p11192
p11192 CO: Free tec_ctrl 1 limit minimum / Ftec1 lim min
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
p11193 Free tec_ctrl 1 limit ramp-up/ramp-down time / Ftec1 lim r-u/r-dn
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 100.00 [s] 1.00 [s]
r11194 CO: Free tec_ctrl 1 output signal / Ftec1 out_sig
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
p11197 CI: Free tec_ctrl 1 limit maximum signal source / Ftec1 lim max s_s
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 11191[0]
p11198 CI: Free tec_ctrl 1 limit minimum signal source / Ftec1 lim min s_s
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 11192[0]