Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
172 List Manual (LH9), 04/2014, A5E33838102B AA
Dependency: Refer to: p0210
Warning: An excessively high value may adversely affect normal drive operation.
Description: Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Note: The Vdc_min controller is not switched back off until the DC-link voltage rises above the threshold 1.05 * p1246 and
the controller output is zero.
Description: Sets the dynamic factor for the Vdc_min controller (kinetic buffering).
100% means that p1250, p1251, and p1252 (gain, integral time, and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, this can be carried out using the dynamic factor. In this case p1250, p1251,
p1252 are weighted with the dynamic factor p1247.
Description: Sets the lower speed threshold for the Vdc_max controller.
When this speed threshold is undershot, the Vdc_max control is switched out and the speed is controlled using the
ramp-function generator.
Note: For fast braking where the ramp-function generator tracking was active, it is possible to prevent the drive rotating in
the opposite direction by increasing the speed threshold and setting a final rounding-off time in the ramp-function
generator (p1131). This is supported using a dynamic setting of the speed controller.
Description: Sets the lower speed threshold for the Vdc_max controller.
When this speed threshold is undershot, the Vdc_max control is switched out and the speed is controlled using the
ramp-function generator.
Note: For fast braking where the ramp-function generator tracking was active, it is possible to prevent the drive rotating in
the opposite direction by increasing the speed threshold and setting a final rounding-off time in the ramp-function
generator (p1131). This is supported using a dynamic setting of the speed controller.
r1246 Vdc_min controller switch-in level (kinetic buffering) / Vdc_min on_level
PM230
PM240, PM330
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6220
Min Max Factory setting
- [V] - [V] - [V]
p1247[0...n] Vdc_min controller dynamic factor (kinetic buffering) / Vdc_min dyn_factor
PM230
PM240, PM330
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6220
Min Max Factory setting
1 [%] 10000 [%] 300 [%]
p1249[0...n] Vdc_max controller speed threshold / Vdc_max n_thresh
PM230
PM240, PM330
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 10.00 [rpm]
p1249[0...n] Vdc_max controller speed threshold / Vdc_max n_thresh
PM250
PM260
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 10.00 [rpm]