841
4 Faults and alarms
4.2 List of faults and alarms
If the value >= r20003, then the sampling time is set to the next higher or the same software sampling time >=
r21003.
Fault value (r0949, interpret decimal):
Number of the p20000 index of the run-time group where the sampling time is incorrectly set.
Number of the run-time group = fault value + 1
Remedy: - correctly set the sampling time of the run-time group.
- if required, take all of the blocks from the run-time group.
Note:
Fault F50518 only detects an incorrectly parameterized run-time group. If, after correcting p20000[i] in the project,
this error occurs again at download, then the run-time group involved should be identified using the fault value
(r0949) and the sampling time correctly set.