Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
440 List Manual, 04/2018, A5E33838102
Description: Sets the minimum limit of the free technology controller 0.
Dependency: Refer to: p11091
Note: The maximum limit must always be greater than the minimum limit (p11091 > p11092).
Description: Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11091, p11092) of the free technology
controller 0.
Dependency: Refer to: p11091, p11092
Note: The ramp-up/ramp-down times are referred to 100%.
Description: Display and connector output for the output signal of the free technology controller 0.
Description: Sets the signal source for the maximum limit of the free technology controller 0.
Dependency: Refer to: p11091
Description: Sets the signal source for the minimum limit of the free technology controller 0.
Dependency: Refer to: p11092
p11092 CO: Free tec_ctrl 0 limit minimum / Ftec0 lim min
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
p11093 Free tec_ctrl 0 limit ramp-up/ramp-down time / Ftec0 lim r-u/r-dn
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 100.00 [s] 1.00 [s]
r11094 CO: Free tec_ctrl 0 output signal / Ftec0 out_sig
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]
p11097 CI: Free tec_ctrl 0 limit maximum signal source / Ftec0 lim max s_s
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 11091[0]
p11098 CI: Free tec_ctrl 0 limit minimum signal source / Ftec0 lim min s_s
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 11092[0]