Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
337
2 Parameters
2.2 List of parameters
Description: Sets the lower value for the adaptation of integral time Tn for the technology controller.
Dependency: Refer to: p2317, p2319, p2320, p2321, r2322
Caution: The upper value must be set higher than the lower value (p2319 > p2318).
Note: Tn adaptation is activated with p2252.8 = 1.
Description: Sets the upper value for the adaptation of integral time Tn for the technology controller.
Dependency: Refer to: p2317, p2318, p2320, p2321, r2322
Caution: The upper value must be set higher than the lower value (p2319 > p2318).
Note: Tn adaptation is activated with p2252.8 = 1.
Description: Sets the lower activation point for the adaptation of integral time Tn for the technology controller.
Dependency: Refer to: p2317, p2318, p2319, p2321, r2322
Caution: The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note: Tn adaptation is activated with p2252.8 = 1.
Description: Sets the upper activation point for the adaptation of integral time Tn for the technology controller.
Dependency: Refer to: p2317, p2318, p2319, p2320, r2322
Caution: The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note: Tn adaptation is activated with p2252.8 = 1.
p2318 Technology controller Tn adaptation lower value / Tn adapt lower val
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
0.000 [s] 60.000 [s] 3.000 [s]
p2319 Technology controller Tn adaptation upper value / Tn adapt upper val
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
0.000 [s] 60.000 [s] 10.000 [s]
p2320 Technology controller Tn adaptation lower starting point / Tn adapt lower pt
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
0.00 [%] 400.00 [%] 0.00 [%]
p2321 Technology controller Tn adaptation upper starting point / Tn adapt upper pt
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
0.00 [%] 400.00 [%] 100.00 [%]