Operating Instructions
Communication via RS485
5.3 Communication via USS
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
119
Parameter number
Parameter numbers < 2000
PNU = parameter number.
Write the parameter number into the PNU (PKE bit 10 ... 0).
Parameter numbers
≥ 2000
PNU = parameter number
- offset.
Write the parameter number minus the offset into the PNU
(PKE bit
10 … 0).
Write the offset in the page index (IND bit 15 … 8).
Table 5- 7 Offset and page index of the parameter numbers
Parameter number
Offset
Page index
Hex
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
0000 … 1999
0
0 hex
0
0
0
0
0
0
0
0
2000 … 3999
2000
80 hex
1
0
0
0
0
0
0
0
6000 … 7999
6000
90 hex
1
0
0
1
0
0
0
0
8000 … 9999
8000
20 hex
0
0
1
0
0
0
0
0
10000 … 11999
10000
A0 hex
1
0
1
0
0
0
0
0
20000 … 21999
20000
50 hex
0
1
0
1
0
0
0
0
30000 … 31999
30000
F0 hex
1
1
1
1
0
0
0
0
60000 … 61999
60000
74 hex
0
1
1
1
0
1
0
0
Indexed parameters
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 7 … 0).
Parameter contents
Parameter contents can be parameter values or connector parameters. You require two
words for connector parameters. You can find more information on interconnecting
connector parameters in the operating instructions of the Control Unit in the section
"Interconnecting signals in the inverter".
Enter the parameter value in the parameter channel right-justified as follows:
•
8-bit values:
Low word, bits
0 … 7,
bits 8
… 15 are zero.
•
16-bit values:
Low word, bits 0 … 15,
•
32-bit values:
Low word and high word
Enter a connector parameter right-justified as follows:
•
Number of the connector parameter:
High word
•
Drive object of the connector parameter:
Low word, bits 10 … 15
•
The index or bit field number of the connector parameter:
Low word, bits 0 … 9