SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Dependency: Refer to: p1035
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the maximum speed/velocity for the motorized potentiometer.
Note: This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value (see function diagram 3020).
Description: Sets the minimum speed/velocity for the motorized potentiometer.
Note: This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value (see function diagram 3020).
Description: Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency: Refer to: p1037, p1038
Note: The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
Description: Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has
been powered up.
Dependency: Only effective if p1030.0 = 0.
Refer to: p1030
p1037[0...n] Motorized potentiometer maximum speed / MotP n_max
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3020
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1038[0...n] Motorized potentiometer minimum speed / MotP n_min
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3020
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1039[0...n] BI: Motorized potentiometer inversion / MotP inv
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3020
Min Max Factory setting
- - 0
p1040[0...n] Motorized potentiometer starting value / Mop start value
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3020
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]