61
2 Parameters
2.2 List of parameters
Dependency: When the motor type is changed, the code number in p0301 may be reset to 0.
When selecting a motor type from the 1LE1, 1LG6, 1LA7, 1LA8, 1LA9 series, parameters p0335, p0626, p0627, and
p0628 of the thermal motor model are pre-assigned as a function of p0307 and p0311.
Caution: If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
Note: Once the Control Unit has been powered up for the first time or if the factory settings have been defined accordingly,
the motor type is pre-configured to induction motor (p0300 = 1).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
Description: The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned
from the internally available parameter lists.
Dependency: Code numbers can only be selected for motor types that correspond to the motor type selected in p0300.
Refer to: p0300
Note: The motor code number can only be changed if the matching catalog motor was first selected in p0300.
When selecting a catalog motor (p0300 >= 100), drive commissioning can only be exited if a code number is
selected.
If a change is made to a non-catalog motor, then the motor code number should be reset (p0301 = 0).
Description: Sets the rated motor voltage (rating plate).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is pre-
assigned to match the power unit.
Description: Sets the rated motor current (rating plate).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0305 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly.
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is pre-
assigned to match the power unit.
p0301[0...n] Motor code number selection / Mot code No. sel
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 0
p0304[0...n] Rated motor voltage / Mot U_rated
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 6301, 6724
Min Max Factory setting
0 [Vrms] 20000 [Vrms] 0 [Vrms]
p0305[0...n] Rated motor current / Mot I_rated
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 6301
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]