Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
317
2 Parameters
2.2 List of parameters
Description: Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency: Refer to: p0015, p3330, p3331, r3333, p3334
Note: The mode of operation of this binector input is dependent on the wire control set in p0015.
Description: Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Dependency: Refer to: p0015, p3330, p3331, p3332, p3334
Description: Sets the two wire control/three wire control.
Value: 0: No wire control
1: Two wire control clockwise/counterclockwise 1
2: Two wire control clockwise/counterclockwise 2
3: Three wire control enable clockwise/counterclockwise
4: Three wire control enable ON/reversing
Dependency: Refer to: p0015, p3330, p3331, p3332, r3333
Note: This value depends on the wire control set in p0015.
Description: Configuration of the DC quantity controller in the overmodulation range.
No DC quantity control for power units that can also be connected through 1 phase to the line supply (r0204.15 = 1).
p3332[0...n] BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2273
Min Max Factory setting
- - 0
r3333.0...3 CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON Yes No -
01 Reversing Yes No -
02 ON inverted Yes No -
03 Reversing inverted Yes No -
p3334 2/3 wire control selection / 2/3 wire select
Access level: 4 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
0 4 0
p3855[0...n] DC quantity controller configuration / DC_ctrl config
PM230
PM240
Access level: 3 Calculated: p0340 = 1,3,5 Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6797
Min Max Factory setting
- - 0111 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DC quantity controller on Yes No -
01 Bandwidth increased Yes No -
02 7. Harmonics reduced Yes No -
03 Filter active Yes No -