Operating Instructions
Commissioning
Safety instructions for commissioning
6
54 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
6 Commissioning
6.1 Safety instructions for commissioning
WARNING
Risk of injury due to uncontrolled movements!
Loads can move uncontrollably when the connected motor is switched on for the
purpose of motor data identification. These movements can cause serious injury.
● Before switching on, check that no parts are loose on the machine or can be
spun out.
● Before switching on, ensure that nobody is working on the machine or located
within the hazardous area around the machine.
● Take measures to prevent unauthorized access to the hazardous area around
the machine.
● Lower hanging/suspended loads to the floor.
6.2 Overview of the commissioning
For detailed information about the commissioning process, please refer to chapter
"Commissioning" in the Operating Instructions for the Control Unit
(A5E34257946B).
The process of commissioning a variable speed drive involves the following steps.
Please carry these out in the specified sequence:
Step Activity Additional information
1
Define the requirements to be met by the
drive for your application [➙ 55].
● Operating Instructions for the Control Unit
(A5E34257946B), Chapter 5.2.3
2
Restore the factory settings on the variable
speed drive if necessary [➙ 74].
● Operating Instructions for the Control Unit
(A5E34257946B), Chapter 5.5
3
Check whether the factory setting of the
drive is appropriate for your application. If
not, start basic commissioning [➙ 55].
● Operating Instructions for the Control Unit
(A5E34257946B), Chapter 5.2.2
4
Check whether you need to adapt the
functions of the terminal strip that you
specify in the basic commissioning.
● Operating Instructions for the Control Unit
(A5E34257946B), Chapter 4.6.5
5
If necessary, adapt the communications
interface in the variable speed drive
[➙ 70].
● Operating Instructions for the Control Unit
(A5E34257946B), Chapter 4.6.7
6
If necessary, set further functions in the
variable speed drive [➙ 74].
● Operating Instructions for the Control Unit
(A5E34257946B), Chapter 6.7
7
Save your settings [➙ 80]. ● Operating Instructions for the Control Unit
(A5E34257946B), Chapter 7
8
Fill out the commissioning log and enclose
it with the plant documentation [➙ 117].