Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
502 List Manual, 04/2018, A5E33838102
Description: Sets the signal source of input quantity X of instance LVM 1 of the double-sided limiter.
Description: Setting parameter for the interval average M of instance LVM 1 of the double-sided limiter.
Description: Setting parameter for the interval limit L of instance LVM 1 of the double-sided limiter.
Description: Setting parameter for hysteresis HY of instance LVM 1 of the double-sided limiter.
Description: Display parameter of instance LVM 1 of the double-sided limiter that input quantity X was at least once X > M + L and
X is >= M + L - HY.
Description: Display parameter of instance LVM 1 of the double-sided limiter that the input quantity X lies within the interval.
p20275 CI: LVM 1 input X / LVM 1 input X
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
- - 0
p20276 LVM 1 interval average value M / LVM 1 avg value M
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
-340.28235E36 340.28235E36 0.0000
p20277 LVM 1 interval limit L / LVM 1 limit L
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
-340.28235E36 340.28235E36 0.0000
p20278 LVM 1 hyst HY / LVM 1 hyst HY
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
-340.28235E36 340.28235E36 0.0000
r20279 BO: LVM 1 input quantity above interval QU / LVM 1 X above QU
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
- - -
r20280 BO: LVM 1 input quantity within interval QM / LVM 1 X within QM
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
- - -