[2]: Measure the motor data at standstill. The inverter switches off the motor after the motor
data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a mechanically limited traversing
range.
[3]: Measure the motor data while the motor is rotating. The inverter switches off the motor
after the motor data identification has been completed.
[11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
[12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
Set the check mark for "RAM data to EEPROM (save data in the drive)" to save your data in
the inverter so that it is not lost if the power fails.
Press the "Finish" button.
You have entered all of the data that is necessary for the quick commissioning of the inverter.