Description: If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Dependency: Refer to: F30002
Description: Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party
motor belonging to a motor list:
1 = Rotating induction motor
2 = Rotating synchronous motor
The type information must be entered to filter motor-specific parameters and to optimize the operating characteris-
tics and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
Value: 0: No motor
1: Induction motor (rotating)
2: Synchronous motor (rotating, permanent-magnet)
10: 1LE1 standard induction motor series
13: 1LG6 standard induction motor series
17: 1LA7 standard induction motor series
19: 1LA9 standard induction motor series
100: 1LE1 standard induction motor
Dependency: When selecting a motor type from the 1LE1, 1LG6, 1LA7, 1LA9 series, parameters p0335, p0626, p0627, and
p0628 of the thermal motor model are pre-assigned as a function of p0307 and p0311.
Note: Once the Control Unit has been powered up for the first time or if the factory settings have been defined accord-
ingly, the motor type is pre-configured to induction motor (p0300 = 1).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
Description: Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party
motor belonging to a motor list:
1 = Rotating induction motor
2 = Rotating synchronous motor
The type information must be entered to filter motor-specific parameters and to optimize the operating characteris-
tics and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
r0297 DC link voltage overvoltage threshold / Vdc U_upper_thresh
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8750, 8760, 8850,
8864, 8950, 8964
Min Max Factory setting
- [V] - [V] - [V]
p0300[0...n] Motor type selection / Mot type sel
PM230
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS, p0130
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0 100 0
p0300[0...n] Motor type selection / Mot type sel
PM330 Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS, p0130
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0 100 0