Operating Instructions
Parameters
List of parameters
1-424
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Setting parameter for the run sequence of instance PDF 0 within the run-time group set in p20171.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source for the input pulse I of instance PDF 1 of the breaking delay device.
Description: Setting parameter for pulse extension time T in milliseconds of instance PDF 1 of the breaking delay device.
Description: Display parameter for output pulse Q of instance PDF 1 of the breaking delay device.
Description: Setting parameter for the run-time group in which the instance PDF 1 of the breaking delay device is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
p20172 PDF 0 run sequence / PDF 0 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7233
Min Max Factory setting
0 32000 460
p20173 BI: PDF 1 input pulse I / PDF 1 inp_pulse I
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7233
Min Max Factory setting
- - 0
p20174 PDF 1 pulse extension time in ms / PDF 1 t_ext ms
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7233
Min Max Factory setting
0.00 5400000.00 0.00
r20175 BO: PDF 1 output Q / PDF 1 output Q
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7233
Min Max Factory setting
- - -
p20176 PDF 1 run-time group / PDF 1 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7233
Min Max Factory setting
5 9999 9999