Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
393
2 Parameters
2.2 List of parameters
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Display and binector output for the output of timer 3 (DTC3).
Where a weekday is deactivated, the following applies (p8430):
- the binector output for this timer is inactive (r8433.0 = 0).
Where a weekday is activated, the following applies (p8430):
- the ON/OFF time setting (p8431, p8432) for this timer has an instant effect on the binector output (r8433).
Dependency: Refer to: p8409, p8430, p8431, p8432
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: For the manual mode: the STW1 (control word 1) entered from the IOP is displayed.
r8433.0...1 BO: RTC DTC3 output / RTC DTC3 output
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Timer on Yes No -
01 Timer ON negated No Yes -
r8540.0...15 BO: STW1 from IOP in the manual mode / STW1 IOP
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Reserved Yes No -
04 Reserved Yes No -
05 Reserved Yes No -
06 Reserved Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Reserved Yes No -
11 Direction reversal (setpoint) Yes No -
12 Reserved Yes No -
13 Reserved Yes No -
14 Reserved Yes No -
15 Reserved Yes No -