Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
315
2 Parameters
2.2 List of parameters
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2185 > p2186
Refer to: p2182, p2186
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
p2185[0...n] Load monitoring torque threshold 1 upper / M_thresh 1 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2186[0...n] Load monitoring torque threshold 1 lower / M_thresh 1 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2187[0...n] Load monitoring torque threshold 2 upper / M_thresh 2 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2188[0...n] Load monitoring torque threshold 2 lower / M_thresh 2 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]