Operating Instructions

4.1.3 Electromechanical components
Surge voltage protection circuit
Connect surge voltage protection circuits to the following components:
Coils of contactors
Relays
Solenoid valves
Motor holding brakes
Connect the surge voltage protection circuit directly at the coil.
Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors
for DC-operated coils.
Installing
4.1 EMC-compliant setup of the machine or plant
Converter with the CU230P-2 Control Units
64 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF