Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
657
4 Faults and alarms
4.1 Overview of faults and alarms
Acknowledging faults
The list of faults and alarms specifies how to acknowledge each fault after the cause has been
removed.
Table 4-3 Acknowledging faults
Acknowledgemen
t
Description
POWER ON The fault is acknowledged via a POWER ON (switch Control Unit off and on again).
Note
If this action has not removed the fault cause, the fault is displayed again immediately after power up.
IMMEDIATELY Faults can be acknowledged as follows:
1 Acknowledge by setting parameter:
p3981 = 0 --> 1
2 Acknowledge via binector inputs:
p2103
p2104
p2105
BI: 1. Acknowledge faults
BI: 2. Acknowledge faults
BI: 3. Acknowledge faults
3 Acknowledge via PROFIBUS control signal:
STW1.7 = 0 --> 1 (edge)
Note
These faults can also be acknowledged by a POWER ON.
If the cause of the fault has not been removed, the fault will continue to be displayed after
acknowledgement.
Safety Integrated faults
The "Safe Torque Off" (STO) function must be deselected before these faults are acknowledged.
PULSE INHIBIT The fault can only be acknowledged when the pulses are inhibited (r0899.11 = 0).
The same options are available for acknowledging as described under acknowledge IMMEDIATELY.