Operating Instructions

List of Parameters
Parameters
1-29
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the actual status for the motor data identification (stationary measurement) and the speed/velocity control-
ler optimization (rotating measurement).
Value: 0: No measurement
115: Measurement q leakage inductance (part 2)
120: Speed controller optimization (vibration test)
140: Calculate speed controller setting
150: Measurement, moment of inertia
170: Measurement, magnetizing current and saturation characteristic
195: Measurement q leakage inductance (part 1)
200: Rotating measurement selected
220: identification, leakage inductance
230: Identification, rotor time constant
240: Identification, stator inductance
250: Identification, stator inductance LQLD
270: Identification, stator resistance
290: Identification, valve lockout time
300: Stationary measurement selected
Note: Re r0047 = 300:
This value is also displayed if encoder calibration p1990 is selected.
Description: Displays the effective Command Data Set (CDS).
Dependency: Refer to: p0810, p0811, r0836
Note: The Command Data Set selected using a binector input (e.g. p0810) is displayed using r0836.
Description: Displays the effective Drive Data Set (DDS).
Dependency: Refer to: p0820, p0821, r0837
Note: When selecting the motor data identification routine and the rotating measurement, the drive data set changeover is
suppressed.
r0047 Motor data ident. routine and speed controller optimization / MotID and n_opt
Access level: 1 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 300 -
r0050.0...1 CO/BO: Command Data Set CDS effective / CDS effective
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS eff., bit 0 ON OFF -
01 CDS eff., bit 1 ON OFF -
r0051.0...1 CO/BO: Drive Data Set DDS effective / DDS effective
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS eff., bit 0 ON OFF -
01 DDS eff., bit 1 ON OFF -