Operating Instructions
Commissioning
Carrying out basic commissioning
6
58 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
You can specify an alternative ramp-down time if necessary.
Activates the motor data identification process. A motor ID process is compulsory
if the CTRL MODE (P1300) has been set to 20 (Sensorless Vector Control).
Motor data identification is initiated when the drive is first enabled following basic
commissioning.
The result of the motor data identification process must be copied from RAM to
ROM! (Options→RAM to ROM)
Confirm that the basic commissioning has been completed. The variable speed
drive will compute the motor data.
1. Press to change the parameter.
2. Use keys and to select "YES".
3. Press to confirm your selection and complete the basic commissioning
process.
Table 11: Commissioning with BOP-2