Operating Instructions
Technical data
Conformity
9
114 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
9.2 Conformity
Environmental conditions
Protection class according to EN 61800-5-1 Class I (with protective conductor system) and
Class III (PELV)
Touch protection according to EN 61800-5-1 If used as intended
Permissible ambient and coolant temperature (air)
during operation for line-side power components
and Power Modules
● Low overload
(low overload LO)
● High overload
(high overload HO)
See derating factors for derating
0 to 40 °C (32 to 104 °F) without derating
> 40 to 60 °C (104 to 160 °F) with derating
0 to 50 °C (32 to 122 °F) without derating
> 50 to 60 °C (122 to 160 °F) with derating
Permissible ambient and coolant temperature (air)
during operation for Control Units and
supplementary system components
● With CU230P-2: 0 to 60 °C (32 to 140 °F)
● With IOP-2-BT: 0 to 50 °C (32 to 122 °F)
● With BOP-2: 0 to 50 °C (32 to 122 °F)
● With SAM: 0 to 50 °C (32 to 122 °F)
● With blanking cover: 0 to 60 °C (32 to 140 °F)
● Up to 2000 m above sea level
Climatic ambient conditions
● Storage (in transport packaging) according to
EN 60721-3-1
● Transport (in transport packaging) according
to EN 60721-3-2
● Operation acc. to EN 60721-3-3
Class 1K3
Temperature -25 to 55 °C (-13 to 131 °F)
Class 2K4
Temperature -40 to 70 °C (104 to 158 °F), max.
humidity 95 % at 40 °C (104 °F)
Class 3K3
Condensation, splashwater, and ice formation
not permitted
(EN 60204, Part 1)
Environmental class/harmful chemical
substances:
● Storage (in transport packaging) according to
EN 60721-3-1
● Transport (in transport packaging) according
to EN 60721-3-2
● Operation acc. to EN 60721-3-3
Class 1C2
Class 2C2
Class 3C2
Organic/biological influences:
● Storage (in transport packaging) according to
EN 60721-3-1
● Transport (in transport packaging) according
to EN 60721-3-2
● Operation acc. to EN 60721-3-3
Class 1B1
Class 2B1
Class 3B1
Degree of pollution according to EN 61800-5-1 2