Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
338 List Manual, 04/2018, A5E33838102
Description: Display and connector output for the output signal of the adaption of integral time Tn for the technology controller.
Dependency: Refer to: p2252, p2317, p2318, p2319, p2320, p2321
Note: Tn adaptation is activated with p2252.8 = 1.
Description: Sets the threshold value for the system deviation of the technology controller, which controls holding the controller
integral component in the range of the skip speeds of the ramp-function generator.
Recommendation: To avoid speed setpoint steps in the range of the skip speeds, we recommend setting p2252 bit 4 = 1 (ramp-function
generator bypass deactivated).
Dependency: The parameter has no effect for p2252 bit 5 = 1 (integrator hold deactivated).
Refer to: r2273
Note: Only p2251 = 0:
If the output signal of the technology controller reaches a skip band in the speed setpoint channel, then the integral
component of the controller is held, if at the same time, the system deviation is lower than the threshold value set
here. By holding the integral component, it can be avoided that the controller oscillates in the range of the skip bands.
Description: Displays the smoothed speed setpoint of the technology controller prior to switching to operation with fault response
(see p2345).
Dependency: Refer to: p2345
Note: Smoothing time = 10 s
Description: Sets the response of the technology controller to the occurrence of fault F07426 (technology controller actual value
limited).
The fault response is executed if status bit 8 or 9 in the technology controller status word r2349 is set. If both status
bits are zero, a switch back to technology controller operation will follow.
Value: 0: Function inhibited
1: On fault: Changeover to r2344 (or p2302)
2: On fault: Changeover to p2215
r2322 CO: Technology controller Tn adaptation output / Tn adapt output
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
- [s] - [s] - [s]
p2339 Techn. controller threshold value f. I comp. hold for skip speed / Tec_ctrl thr_skip
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: 9_1 Unit selection: p0595 Func. diagram: -
Min Max Factory setting
0.00 [%] 200.00 [%] 2.00 [%]
r2344 CO: Technology controller last speed setpoint (smoothed) / Tec_ctrl n_setp_sm
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- [%] - [%] - [%]
p2345 Technology controller fault response / Tech_ctrl flt resp
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0 2 0