SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the stator leakage time constant.
Note: The value is calculated from the total of all leakage inductances (p0233, p0356, p0358) divided by the total of all
motor resistances (p0350, p0352, p0354). The temperature adaptation of the resistances is not taken into account.
Description: Displays the actual stator resistance (phase value).
The parameter value also contains the temperature-independent cable resistance.
Dependency: In the case of induction motors the parameter is also affected by the motor temperature model.
Refer to: p0350, p0352, p0620
Note: In each case, only the stator resistance of the active Motor Data Set is included with the stator temperature of the
thermal motor model.
Description: Displays the actual rotor resistance (phase value).
The parameter is affected by the motor temperature model.
Dependency: Refer to: p0354, p0620
Note: In each case, only the rotor resistance of the active Motor Data Set is included with the rotor temperature of the
thermal motor model.
This parameter is not used for synchronous motors (p0300 = 2xx).
Description: Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0340 = 5.
Value: 3: Pumps and fans, efficiency optimization
Notice: If the technological application is set to p0500 = 0 ... 3 during commissioning (p0010 = 1, 5, 30), the operating mode
(p1300) is pre-set accordingly.
Note: The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5
r0386[0...n] Motor stator leakage time constant / Mot T_stator leak
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [ms] - [ms] - [ms]
r0395[0...n] Actual stator resistance / R_stator act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0396[0...n] Actual rotor resistance / R_rotor act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 6730
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0500 Technology application / Tec application
PM230 Access level: 4 Calculated: - Data type: Integer16
Can be changed: C(1, 5), T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
3 3 3