Operating Instructions
Parameters
List of parameters
1-32
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the saved energy referred to 100 operating hours.
Dependency: Refer to: p0040
Note: This display is used for a fluid-flow machine.
The flow characteristic is entered into p3320 ... p3329.
For an operating time of below 100 hours, the display is interpolated up to 100 hours.
Description: Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
Description: Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
Dependency: Refer to: r0002
Note: The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a "switching on inhibited".
r0041 Energy consumption saved / Energy cons saved
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [kWh] - [kWh] - [kWh]
p0045 Display values smoothing time constant / Disp_val T_smooth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6714, 8012
Min Max Factory setting
0.00 [ms] 10000.00 [ms] 4.00 [ms]
r0046.0...31 CO/BO: Missing enable sig / Missing enable sig
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2634
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 OFF1 enable missing Yes No -
01 OFF2 enable missing Yes No -
02 OFF3 enable missing Yes No -
03 Operation enable missing Yes No -
04 DC braking enable missing Yes No -
10 Ramp-function generator enable missing Yes No -
11 Ramp-function generator start missing Yes No -
12 Setpoint enable missing Yes No -
16 OFF1 enable internal missing Yes No -
17 OFF2 enable internal missing Yes No -
18 OFF3 enable internal missing Yes No -
19 Pulse enable internal missing Yes No -
20 DC braking internal enable missing Yes No -
21 PU enab missing Yes No -
25 Function bypass active Yes No -
26 Drive inactive or not operational Yes No -
27 De-magnetizing not completed Yes No -
30 Speed controller inhibited Yes No -
31 Jog setpoint active Yes No -