Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
60 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = Induction motor
2 = Synchronous motor
6 = Synchronous reluctance motor
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
Value: 0: No motor
1: Induction motor
2: Synchronous motor
6: Reluctance motor
10: 1LE1 induction motor
13: 1LG6 induction motor
17: 1LA7 induction motor
19: 1LA9 induction motor
100: 1LE1 induction motor
600: 1FP1 reluctance motor
Dependency: When selecting a motor type from the 1LE1, 1LG6, 1LA7, 1LA9 series, parameters p0335, p0626, p0627, and p0628
of the thermal motor model are pre-assigned as a function of p0307 and p0311.
Caution: If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
Note: Once the Control Unit has been powered up for the first time or if the factory settings have been defined accordingly,
the motor type is pre-configured to induction motor (p0300 = 1).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
Description: Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = Induction motor
2 = Synchronous motor
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
Value: 0: No motor
1: Induction motor
2: Synchronous motor
10: 1LE1 induction motor
13: 1LG6 induction motor
14: 1xx1 SIMOTICS FD induction motor
17: 1LA7 induction motor
18: 1LA8 / 1PQ8 standard induction motor series
19: 1LA9 induction motor
100: 1LE1 induction motor
p0300[0...n] Motor type selection / Mot type sel
PM240 Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS, p0130
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0 600 0
p0300[0...n] Motor type selection / Mot type sel
PM330 Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS, p0130
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0 100 0