Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
214 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the configuration for the adaptation circuit of the motor model.
Induction motor (ASM): Rs, Lh, and offset compensation.
Dependency: In U/f characteristic operating mode only bit 7 is relevant.
For active motor model feedback (see p1784), the Lh adaptation is internally deactivated automatically.
Note: ASM: Induction motor
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is de-
activated and is instead taken into account in the motor model.
In order that the correction values of the Rs and Lh adaptation (selected using bit 0 ... bit 1) are correctly accepted
when changing over the drive data set, a dedicated motor number must be entered into p0826 for each different
motor.
Description: Sets the configuration for the adaptation circuit of the motor model.
Induction motor (ASM): Rs, Lh, and offset compensation.
Dependency: In U/f characteristic operating mode, only bit 7 and bit 11 are relevant.
For active motor model feedback (see p1784), the Lh adaptation is internally deactivated automatically.
Note: ASM: Induction motor
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is de-
activated and is instead taken into account in the motor model.
In order that the correction values of the Rs and Lh adaptation (selected using bit 0 ... bit 1) are correctly accepted
when changing over the drive data set, a dedicated motor number must be entered into p0826 for each different
motor.
p1780[0...n] Motor model adaptation configuration / MotMod adapt conf
PM230
PM240
PM250, PM260
Access level: 4 Calculated: p0340 = 1,3,4 Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0001 0100 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Select motor model ASM Rs adaptation Yes No -
02 Select motor model ASM Lh adaptation Yes No -
04 Select motor model offset adaptation Yes No -
07 Select T(valve) with Rs adaptation Yes No -
10 Filter time combination current like current
ctrl integral time
Yes No -
14 Delay of the precontrol speed to the motor
model
Yes No -
15 RESM: Linear Q flux model active not active -
p1780[0...n] Motor model adaptation configuration / MotMod adapt conf
PM330 Access level: 3 Calculated: p0340 = 1,3,4 Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 1000 0001 0100 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Select motor model ASM Rs adaptation Yes No -
02 Select motor model ASM Lh adaptation Yes No -
04 Select motor model offset adaptation Yes No -
07 Select T(valve) with Rs adaptation Yes No -
10 Filter time combination current like current
ctrl integral time
Yes No -
11 Fast flying restart with voltage model for
induction motor
Yes No -