Installation Instructions

Table Of Contents
Connecting
5.3 Connecting the line and motor cable at the inverter
PM230 Power Module, IP55
Hardware Installation Manual, 12/2016, A5E35319202B AB
35
2. Remove the cable gland plate from the bottom of the inverter.
Diameters of the drill holes in the cable gland plates:
20.5 mm
Control cables
20.5 mm
Mains and motor cables, FSA
25.5 mm
Mains and motor cables, FSB
32.5 mm
Mains and motor cables, FSC
Figure 5-3 Bolting plates for PM230, FSA to FSC
3. Prepare the mains and motor cables for connection in accordance with the table below.
Inverter
Connection
Dimensions
Explanation
A
B
C
1)
D
FSA
Mains cable
10 mm
60 mm
-
90 mm
Motor cable
10 mm
60 mm
10 mm
60 mm
FSB
Mains cable
10 mm
60 mm
-
50 mm
Motor cable
10 mm
50 mm
10 mm
40 mm
FSC
Mains cable
10 mm
50 mm
-
70 mm
Motor cable 10 mm 50 mm 10 mm 40 mm
1)
Cable shield
Bolting plate
4. Assemble the cable glands with the prepared cables and EMC cable glands for the
control cables.
5. Seal any unused bushings with a rubber sleeve.
6. Secure the bolting plate to the inverter enclosure. Tightening torque: 2 Nm
Make sure that the seal of the bolting plate is not damaged.