Operating Instructions
Installing
Installing the Power Module
5
36 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
Figure 11: IP55 FSD-FSF
Item Designation Item Designation
1
Connection of supply voltage
2
Motor connection
Overview of tightening torques
FSA FSB FSC FSD FSE FSF
IP20 0.4 Nm...
0.5 Nm
0.55 Nm...
0.6 Nm
1.2 Nm...
1.5 Nm
6 Nm 6 Nm 13 Nm
IP55 0,5 Nm
(4,4 lbf.in)
0,6 Nm
(5,3 lbf.in)
1,5 Nm
(13,3 lbf.in)
M6: 6 Nm
(53,0 lbf.in)
M6: 6 Nm
(5,3 lbf.in)
M8: 13 Nm
(115 lbf.in)
Table 9: Overview of tightening torques
5.3.2.2 Overview of motor cable lengths and cross sections
The following tables contain all relevant information about required cable lengths
and cross sections. Adherence to the specified values is essential in order to
ensure that the installation complies with EMC regulations.
PM230 Cable type EMC category Max. cable length
Filter A Shielded C2 25 m (80 ft)
Shielded C3 50 m (164 ft)
Unshielded No 100 m (330 ft)
Filter B Shielded C1
(conducted only)
25 m (80 ft) with IP54
50 m (164 ft) with IP20
Shielded C2 50 m (164 ft)
Unshielded No 100 m (330 ft)
● You may only use copper wire of class 1, 75 °C (for compliance with the UL in
frame sizes A to C).
● Ensure that the appropriate circuit breakers or fuses with the specified current
rating are connected between the power supply and the drive.
IP55 FSD...FSF
Cable specifications