Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
232 List Manual, 04/2018, A5E33838102
Description: Displays the actual maximum possible electromotive force (EMF) of the separately excited synchronous motor.
Dependency: The value is the basis for the flux setpoint.
The maximum possible EMF depends on the following factors:
- Actual DC link voltage (r0070).
- Maximum modulation depth (p1803).
- Field-generating and torque-generating current setpoint.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description: Sets the smoothing time for the current setpoint.
The current setpoint is generated from p1610 and p1611.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: This parameter is only effective in the range where current is injected for sensorless vector control.
Description: Displays the steady-state field generating current setpoint (Id_set).
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: For index 1:
Reserved.
Description: Displays the limited field-generating current setpoint (Id_set).
This value comprises the steady-state field-generating current setpoint r1623 and a dynamic component that is only
set when changes are made to the flux setpoint.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
r1614 EMF maximum / EMF max
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_1 Unit selection: p0505 Func. diagram: 6725
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p1616[0...n] Current setpoint smoothing time / I_set T_smooth
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6721, 6722
Min Max Factory setting
4 [ms] 10000 [ms] 40 [ms]
r1623[0...1] Field-generating current setpoint (steady-state) / Id_set stationary
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: 6_2 Unit selection: p0505 Func. diagram: 6723
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r1624 Field-generating current setpoint total / Id_setp total
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: 6_2 Unit selection: p0505 Func. diagram: 6640, 6721, 6723,
6727
Min Max Factory setting
- [Arms] - [Arms] - [Arms]