Operating Instructions

Communication via AS-i - only for G110M
7.3 Dual Slave mode
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
223
If the control sends a diagnostic request via AS-i.P0, the inverter replies with the currently
pending fault or alarm messages.
Table 7-5 Alarm and fault messages via RP0 … RP3 from the inverter to the AS-i
master (Page 225).
Default setting 34, slave 1 with profile 7.A.5: Control -> inverter
AS-i.DO0
-
>
Time signal for the CTT2 transfer from the AS
-i master
AS-i.DO1
-
>
Data bit
for the CTT2 transfer, four bytes cyclically or acyclically via
PIV. The reading and writing of parameters is possible via the PIV.
Because data is transferred bit
-by-bit, the read and write process is
very slow.
AS-i.DO2
-
>
p0881 = 2093.4
Override quick
stop
AS-i.DO3
-
>
Select slave A or slave B, interconnected internally
Default setting 34, slave 1 with profile 7.A.5: Inverter -> control
p2080[4] = 722.2
State DI2
-
>
AS
-i.DI0
p2080[5] = 722.3
State DI3
-
>
AS
-i.DI1
Serial data transfer CTT2, four bytes cyclically or acyclically via PIV.
The reading and writing of parameters is possible via the PIV.
Because data is transferred bit-by-bit, the read and write process is
very slow.
-
>
AS
-i.DI2
Time signal for the CTT2 transfer to the AS-i master
-
>
AS
-i.DI3