Operating Instructions
List of parameters
Parameters
1-313
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the signal source for the direction of rotation during essential service mode (ESM).
p3883 = 1 signal:
Direction of rotation of the setpoint, parameterized for essential service mode, is reversed.
p3883 = 0 signal:
Direction of rotation of the setpoint parameterized for essential service mode is kept.
Warning: The direction reversal is not taken into account if p3881 = 4 is set (technology controller) and the technology con-
troller is also active as the setpoint source.
Note: ESM: Essential Service Mode
Description: Sets the signal source for the setpoint for p3881 = 4 (technology controller) in the essential service mode (ESM).
Dependency: Refer to: p3881
Note: ESM: Essential Service Mode
Re p3884 = 0:
The technology controller uses the setpoint from p2253.
Description: Displays the number of activations and faults that have occurred for the essential service mode (ESM).
Index: [0] = Activation of the essential service mode
[1] = Faults during the essential service mode
Dependency: Refer to: p3888
Note: ESM: Essential Service Mode
Description: Setting to reset the number of activations and faults that have occurred for the essential service mode (ESM).
1: counter reset active (r3887[0, 1])
0: inactive
Dependency: Refer to: r3887
p3883 BI: ESM direction of rotation signal source / ESM rot dir s s
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
- - 0
p3884 CI: ESM setpoint technology controller / ESM setp tech_ctrl
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
- - 0
r3887[0...1] ESM number of activations/faults / ESM act/fault qty
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
- - -
p3888 ESM reset number of activations/faults / ESM act/F qty r
Access level: 4 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
0 1 0