Installation Instructions

Table Of Contents
Routing cables outside the control cabinet
Maintain a minimum clearance of 25 cm between cables with a high level of interference
and cables with a low level of interference.
Using shielded cables for the following connections:
Inverter motor cable
Cable between the inverter and braking resistor
Signal and data cables
Connect the motor cable shield to the motor enclosure using a PG gland that establishes
a good electrical connection.
Requirements relating to shielded cables
Use cables with finely-stranded, braided shields.
Connect the shield to at least one end of the cable.
%DUHVKLHOG
0RXQWLQJSODWH
6KLHOGSODWH
&RQQHFWVKLHOG
7RRWKHG
WDSH
+RVHFODPS
Figure 4-4 Examples for EMC-compliant shield support
Attach the shield to the shield support directly after the cable enters the cabinet.
Do not interrupt the shield.
Only use metallic or metallized plug connectors for shielded data cables.
Installing/mounting
4.2 EMC-compliant installation of a plant or machine
Power Module PM230, IP20 / Push-through technology (PT)
Hardware Installation Manual, 08/2016, A5E34331322B AB 27