Table 6- 5 TPDO configuration objects - communication parameters
OD
index
(hex)
Sub-
index
(hex)
Object name
SINAMICS
parameters
Data
type
Predefined con-
nection set
Can be
read/
written
1800
Transmit PDO 1 communication parameter
0 Largest subindex supported U8 5 r
1 COB ID used by PDO p8720.0 U32 180 hex + node
ID
r/w
2 Transmission type p8720.1 U8 FE hex r/w
3
Inhibit time
p8720.2
U16
0
r/w
4
Reserved
p8720.3
U8
---
r/w
5
Event timer
p8720.4
U16
0
r/w
1801
Transmit PDO 2 communication parameter
0
Largest subindex supported
U8
5
r
1 COB ID used by PDO p8721.0 U32 280 hex + node
ID
r/w
2
Transmission type
p8721.1
U8
FE hex
r/w
3
Inhibit time
p8721.2
U16
0
r/w
4
Reserved
p8721.3
U8
---
r/w
5
Event timer
p8721.4
U16
0
r/w
1802
Transmit PDO 3 communication parameter
0
Largest subindex supported
U8
5
r
1
COB ID used by PDO
p8722.0
U32
C000 06DF hex
r/w
2
Transmission type
p8722.1
U8
FE hex
r/w
3
Inhibit time
p8722.2
U16
0
r/w
4
Reserved
p8722.3
U8
---
r/w
5 Event timer p8722.4 U16 0 r/w
1803
Transmit PDO 4 communication parameter
0 Largest subindex supported U8 5 r
1
COB ID used by PDO
p8723.0
U32
C000 06DF hex
r/w
2
Transmission type
p8723.1
U8
FE hex
r/w
3
Inhibit time
p8723.2
U16
0
r/w
4
Reserved
p8723.3
U8
---
r/w
5
Event timer
p8723.4
U16
0
r/w
1804
Transmit PDO 5 communication parameter
0
Largest subindex supported
U8
5
r
1
COB ID used by PDO
p8724.0
U32
C000 06DF hex
r/w
2
Transmission type
p8724.1
U8
FE hex
r/w