Installation Instructions
Table Of Contents
- Power Module PM230, IP20 / Push-through technology (PT)
- Legal information - Warning notice system
- Table of contents
- 1 Changes in this manual
- 2 Fundamental safety instructions
- 3 Introduction
- 4 Installing/mounting
- 5 Connecting
- 6 Service and maintenance
- 7 Technical specifications
- 7.1 Overload capability of the inverter
- 7.2 Cable cross-sections and tightening torques
- 7.3 Electromagnetic compatibility - overview
- 7.4 Ambient conditions
- 7.5 General technical data
- 7.6 Detailed technical data
- 7.7 Restrictions for special ambient conditions
- 7.8 Electromagnetic compatibility of variable-speed drives
- 8 Spare parts and accessories
- A Appendix
- Index

Table 8-2 Technical data
Article number P
loss
1)
(W)
Connection Degree of
protection
Power Module / motor
6SL3202-0AE26-2SA0 65 Screw terminals 25 … 50 mm
2
IP20
6SL3202-0AE28-8SA0 100 Screw terminals 25 … 95 mm
2
IP20
6SL3202-0AE31-5SA0 180 Screw terminals 50 … 150 mm
2
IP20
6SL3202-0AE31-8SA0 190 Screw terminals 50 … 150 mm
2
IP20
1)
Power loss at 50 Hz
Table 8-3 Assignment table
Power Module Sine-wave filters
Article number Power (kW) Frame size Article number
6SL3210-1NE24-5 . L0 22 FSD 6SL3202-0AE26-2SA0
6SL3210-1NE26-0 . L0
6SL3210-1NE27-5 . L0
30
37
FSD
FSE
6SL3202-0AE28-8SA0
6SL3210-1NE28-8 . L0
6SL3210-1NE31-1 . L0
45
55
FSE
FSF
6SL3202-0AE31-5SA0
6SL3210-1NE31-5 . L0 75 FSF 6SL3202-0AE31-8SA0
8.3.4 Output reactors
When using the output reactor it is not permissible that the output frequency exceeds 150 Hz.
It is not permissible that the pulse frequency exceeds 4 kHz
Mounting position
Spare parts and accessories
8.3 Optional accessories
Power Module PM230, IP20 / Push-through technology (PT)
84 Hardware Installation Manual, 08/2016, A5E34331322B AB