Installation Instructions
Table Of Contents
- Power Module PM230, IP20 / Push-through technology (PT)
- Legal information - Warning notice system
- Table of contents
- 1 Changes in this manual
- 2 Fundamental safety instructions
- 3 Introduction
- 4 Installing/mounting
- 5 Connecting
- 6 Service and maintenance
- 7 Technical specifications
- 7.1 Overload capability of the inverter
- 7.2 Cable cross-sections and tightening torques
- 7.3 Electromagnetic compatibility - overview
- 7.4 Ambient conditions
- 7.5 General technical data
- 7.6 Detailed technical data
- 7.7 Restrictions for special ambient conditions
- 7.8 Electromagnetic compatibility of variable-speed drives
- 8 Spare parts and accessories
- A Appendix
- Index

Routing cables outside the control cabinet
● Maintain a minimum clearance of 25 cm between cables with a high level of interference
and cables with a low level of interference.
● Using shielded cables for the following connections:
– Inverter motor cable
– Cable between the inverter and braking resistor
– Signal and data cables
● Connect the motor cable shield to the motor enclosure using a PG gland that establishes
a good electrical connection.
Requirements relating to shielded cables
● Use cables with finely-stranded, braided shields.
● Connect the shield to at least one end of the cable.
%DUHVKLHOG
0RXQWLQJSODWH
6KLHOGSODWH
&RQQHFWVKLHOG
7RRWKHG
WDSH
+RVHFODPS
Figure 4-4 Examples for EMC-compliant shield support
● Attach the shield to the shield support directly after the cable enters the cabinet.
● Do not interrupt the shield.
● Only use metallic or metallized plug connectors for shielded data cables.
Installing/mounting
4.2 EMC-compliant installation of a plant or machine
Power Module PM230, IP20 / Push-through technology (PT)
Hardware Installation Manual, 08/2016, A5E34331322B AB 27