Data Sheet for Product
12
Siemens
N5111
2021-12-14
Technical data
Functional data
Electrical data
Power (low overload LO)
0.75 to 90 kW
Line voltage
380 to 480 V 3 AC ±10 %
Line frequency
47 to 63 Hz
Overload capability of frame sizes A – C
(low overload LO)
● 1.5 x base-load current (150 %) for 3 s every 300 s
● 1.1 x base-load current (110%) for 57 s every 300 s
Overload capability of frame sizes D – F
(low overload LO)
1.1 x base-load current (110%) for 60 s every 300 s
Rated input current
(LO: at 40 ℃)
2.3 to 166 A (IP55)
2.3 to 135 A (IP20)
Base-load current
LO: at 40 ℃)
2.2 to 178 A (IP55)
2.2 to 145 A (IP20)
Operating temperature
0 to 60 °C while derating
(see derating factors)
Relative humidity
< 95% RH, non-condensing
Output frequency
0 to 550 Hz
Pulse frequency
4 kHz (default) to 16 kHz. The pulse frequency can be
changed manually in 2 kHz steps.
Frequency range that can be skipped
4, parameterizable
Fixed frequencies
15, parameterizable
Digital inputs and outputs
● 6 DI
● 3 DO (2 x 230 V AC / 2 A, 1 x 30 V DC / 0.5 A)
● 4 AI (2 x 0 to 10 V / -10 to 10 V / 0 to 20 mA / 4 to
20 mA, 1 x 0 to 20 mA / 4 to 20 mA / Pt1000 /
LG-Ni1000, 1 x Pt1000 / LG-Ni1000)
● 2 AO (0 to 10 V / 0 to 20 mA / 4 to 20 mA)
● 1 x KTY/PTC/ThermoClick sensor
● 2 x PSU-out (10 VDC, 24 VDC)
● 1 x PSU-in (24 VDC)
Short-circuit current rating (SCCR)
IP55 FSA - FSC: 40kA
IP55 FSD - FSF: 65kA
IP20 FSA - FSF: 65kA
Mechanical data
Vibratory load
● Transport (in transport packaging) according to
EN 60721-3-2
● Operation
Test values according to EN 60068-2-6
Class 2M3
Class 3M2
Shock stressing
● Transport (in transport packaging) according to
EN 60721-3-2
All devices and components
● Operation
Test values according to EN 60068-2-6
Frame sizes A to F
Class 2M3
Class 3M2