Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
162 List Manual, 04/2018, A5E33838102
Description: Sets the signal source for lowest possible motor speed.
Dependency: Refer to: p1080
Notice: The effective minimum speed is formed from p1080 and p1106.
Description: Sets the signal source to select the total setpoint.
Dependency: The selection of the total speed setpoint is automatically interconnected to the status word of the technology
controller (r2349.4) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the "hibernation mode" function is activated (p2398 = 1), an interconnection is made to r2399.7.
Refer to: p1109
Caution: If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the
interconnection to its status word (r2349.4).
If the "hibernation mode" function is activated, then it is not permissible to disable the interconnection to status word
r2399.
Description: Sets the signal source for the total setpoint.
For p1108 = 1 signal, the total setpoint is read in via p1109.
Dependency: The signal source of the total setpoint is automatically interconnected to the output of the technology controller
(r2294) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the "hibernation mode" function is activated (p2398 = 1), an interconnection is made to r2397[0].
Refer to: p1108
Caution: If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the
interconnection to its output (r2294).
If the "hibernation mode" function is activated, then it is not permissible to withdraw the interconnection to setpoint
r2398[0].
Description: Sets the signal source to disable the negative direction.
Dependency: Refer to: p1111
p1106[0...n] CI: Minimum speed signal source / n_min s_src
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3050
Min Max Factory setting
- - 0
p1108[0...n] BI: Total setpoint selection / Total setp sel
Access level: 4 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3030
Min Max Factory setting
- - 0
p1109[0...n] CI: Total setpoint / Total setp
Access level: 4 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 3030
Min Max Factory setting
- - 0
p1110[0...n] BI: Inhibit negative direction / Inhib neg dir
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2505, 3040
Min Max Factory setting
- - 1