Operating Instructions

List of Parameters
Parameters
1-231
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the phase sequence reversal for the motor without setpoint change.
If the motor does not rotate in the required direction, then the output phase sequence can be reversed using this
parameter. This means that the direction of the motor is reversed without the setpoint being changed.
Value: 0: OFF
1: ON
Note: This setting can only be changed when the pulses are inhibited.
Description: Sets the threshold voltage drop of the valves (power semiconductor devices) to be compensated.
Note: The value is automatically calculated in the motor data identification routine.
Description: Sets the valve lockout time to compensate for phase U.
Note: The value is automatically calculated in the motor data identification routine.
Description: Sets the valve lockout time to compensate for phase V.
Description: Sets the valve lockout time to compensate for phase W.
p1820[0...n] Reverse the output phase sequence / Outp_ph_seq rev
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(2), T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 1 0
p1825 Converter valve threshold voltage / Threshold voltage
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.0 [Vrms] 100.0 [Vrms] 0.6 [Vrms]
p1828 Compensation valve lockout time phase U / Comp t_lock ph U
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 [µs] 3.99 [µs] 0.00 [µs]
p1829 Compensation valve lockout time phase V / Comp t_lock ph V
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 [µs] 3.99 [µs] 0.00 [µs]
p1830 Compensation valve lockout time phase W / Comp t_lock ph W
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 [µs] 3.99 [µs] 0.00 [µs]