Operating Instructions

4 Faults and alarms
4.1 Overview of faults and alarms
SINAMICS G120 CU230P-2 Control Units
654 List Manual (LH9), 04/2014, A5E33838102B AA
4.1 Overview of faults and alarms
4.1.1 General information
Fault and alarm displays (messages)
In the case of a fault, the drive signals the corresponding fault(s) and/or alarm(s).
For example, the following methods for displaying faults and alarms are available:
Display via the fault and alarm buffer with PROFIBUS/PROFINET
Display online via the commissioning software
Display and operating unit (e.g. BOP, AOP)
Differences between faults and alarms
The differences between faults and alarms are as follows:
Table 4-1 Differences between faults and alarms
Type Description
Faults What happens when a fault occurs?
The appropriate fault reaction is triggered.
Status bit ZSW1.3 is set.
The fault is entered in the fault buffer.
How are faults eliminated?
Remove the original cause of the fault.
Acknowledge the fault.
Alarms What happens when an alarm occurs?
Status signal ZSW1.7 is set.
The alarm is entered in the alarm buffer.
How are alarms removed?
Alarms acknowledge themselves.
If the cause of the alarm is no longer present, they automatically reset
themselves.