Description: Displays the status word of the free technology controller 2.
Description: Sets the signal source for the setpoint of the free technology controller 2.
Description: Sets the ramp-up time for the free technology controller 2.
Dependency: Refer to: p11258
Note: The ramp-up time is referred to 100 %.
Description: Sets the ramp-down time of the free technology controller 2.
Dependency: Refer to: p11257
Note: The ramp-down time is referred to 100 %.
Description: Display and connector output for the setpoint after the ramp-function generator of the free technology controller 2.
r11249.0...11 CO/BO: Free tec_ctrl 2 status word / Ftec2 stat_word
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Deactivated Yes No -
01 Limited Yes No -
08 Actual value at the minimum Yes No -
09 Actual value at the maximum Yes No -
10 Output at the minimum Yes No -
11 Output at the maximum Yes No -
p11253 CI: Free tec_ctrl 2 setpoint signal source / Ftec2 setp s_src
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 0
p11257 Free tec_ctrl 2 setpoint ramp-up time / Ftec2 setp t_r-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
p11258 Free tec_ctrl 2 setpoint ramp-down time / Ftec2 setp t_r-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
r11260 CO: Free tec_ctrl 2 setpoint after ramp-function generator / Ftec2 setp aft RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_4 Unit selection: p11226 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]