Operating Instructions
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI (https://
support.industry.siemens.com/cs/ww/en/view/60441457)
Controlling the speed of a SINAMICS G110M / G120 (Startdrive) with S7-1500 (TO) via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI (https://
support.industry.siemens.com/cs/ww/en/view/78788716)
4.5.11.3 Installing the GSD
Procedure
1. Save the GSD on your PC via one of the following methods.
– With Internet access:
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
– Without Internet access:
Insert a memory card into the inverter.
Set p0804 to 12.
The inverter writes the GSD as zipped file (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
2. Unzip the GSD file on your computer.
3. Import the GSD in the engineering system of the controller.
You have now installed the GSD file in the engineering system of the controller.
❒
4.5.11.4 Setting the address
Valid address area: 1 … 125
You have the following options for setting the address:
● Using the address switch on the Control Unit:
([DPSOH
2II
%LW
%LW
%LW
%LW
%LW
%LW
%LW
2II2Q2Q
Figure 4-34 Address switch with example for bus address 10
The address switch has priority over the other settings.
● Using Startdrive or an operator panel via parameter p0918 (default setting: p0918 = 126)
It is only possible to change p0918 if an invalid address is set in the address switch.
If you are working with Startdrive, back up the settings so they are not lost if the power fails.
Overview of the interfaces (Page 114)
Installing
4.5 Connecting the interfaces for the inverter control
Converter with the CU230P-2 Control Units
148 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF